1. Study on a two-evaporator system for humidity control.
- Author
-
Fye, Chan Kar, Raghavan, Vijay R., and Meng, Chin Wai
- Subjects
- *
EVAPORATORS , *HUMIDITY control , *PERFORMANCE evaluation , *COOLING , *AIR conditioning , *FEASIBILITY studies , *INLETS , *REFRIGERANTS - Abstract
A feasibility study was performed on a two-evaporator system for humidity control. The two-evaporator system considered requires the addition of a reheat coil to the conventional unit. The reheat coil serves to reheat the cooled air leaving the cooling coils, thereby controlling the relative humidity. An experimental study was performing using a modified commercial ceiling concealed air conditioning unit. Results from the experiments show that the dehumidification capability is improved by 11%. However, the cooling performance was reduced by 13%. It is possible to control the relative humidity of the leaving air by adjusting the refrigerant temperature at the inlet of the reheat coil but at the cost of cooling performance. [ABSTRACT FROM AUTHOR]
- Published
- 2012
- Full Text