Study on a two-evaporator system for humidity control.
- Source :
-
AIP Conference Proceedings . 6/30/2012, Vol. 1440 Issue 1, p361-369. 9p. - Publication Year :
- 2012
-
Abstract
- A feasibility study was performed on a two-evaporator system for humidity control. The two-evaporator system considered requires the addition of a reheat coil to the conventional unit. The reheat coil serves to reheat the cooled air leaving the cooling coils, thereby controlling the relative humidity. An experimental study was performing using a modified commercial ceiling concealed air conditioning unit. Results from the experiments show that the dehumidification capability is improved by 11%. However, the cooling performance was reduced by 13%. It is possible to control the relative humidity of the leaving air by adjusting the refrigerant temperature at the inlet of the reheat coil but at the cost of cooling performance. [ABSTRACT FROM AUTHOR]