Influence of the ICFF decoupling technique on the stability of the current control loop of a grid-tied VSC
Influence of the ICFF decoupling technique on the stability of the current control loop of a grid-tied VSC
- Publication Year :
- 2019
-
Abstract
- © 2019 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other uses, in any current or future media, including reprinting/republishing this material for advertising or promotional purposes,creating new collective works, for resale or redistribution to servers or lists, or reuse of any copyrighted component of this work in other works.<br />The control scheme of grid-tied converters is often implemented in the dq-frame due to simplicity of design. However, with this transformation, there exists an inherent cross-coupling term between the d-and q-channels which is often compensated for by using a feed-forward term in the current-control loop. It is shown, by applying the generalized Nyquist criterion (GNC) to the dq-frame ac impedance of the converter, that the inclusion of this decoupling term, in fact, degrades the stability of the controller when increasing the bandwidth of the synchronous reference frame phase-locked loop (SRF-PLL). Harware-in-the-loop (HIL) experiments are also conducted and verify these results.<br />Peer Reviewed<br />Postprint (author's final draft)