Back to Search Start Over

Testing of algorithms for a stand-alone digital relay for power transformers

Authors :
Rahman, M.A.
So, B.
Zaman, M.R.
Hoque, M.A.
Source :
IEEE Transactions on Power Delivery. April, 1998, Vol. 13 Issue 2, p374, 12 p.
Publication Year :
1998

Abstract

A stand-alone digital relay has been designed and implemented. The relay can be modified easily to accommodate the protection of different types of transformers by changing the software only. Presented in this paper are the real-time experimental results of five selected algorithms implemented using this digital relay. These algorithms are: discrete Fourier transform, Walsh function, rectangular transform, finite impulse response and least-square. based on the experimental results, the discrete Fourier transform (DFT) algorithm is found to be the best algorithm in terms of accuracy and speed for digital implementation of the differential relay for power transformers. Keywords: Digital relay, power transformer, differential protection, testing algorithms.