Back to Search Start Over

Harmonic resonance on parallel high voltage transmission lines

Authors :
Harries, J.R.
Randall, J.L.
Source :
IEEE Transactions on Power Delivery. Jan, 1997, Vol. 12 Issue 1, p477, 6 p.
Publication Year :
1997

Abstract

Harmonic resonance has been observed, measured and modeled on parallel 500-kV lines that are about one wavelength at 2100 Hz, the 35th harmonic. A seemingly small harmonic injection at one location on the system causes significant problems some distance away such as telephone interference.

Details

ISSN :
08858977
Volume :
12
Issue :
1
Database :
Gale General OneFile
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
edsgcl.19267268