A new strategy for determining fault zones in distance relays
- Source :
- IEEE Transactions on Power Delivery. Oct, 2008, Vol. 23 Issue 4, p1857, 7 p.
- Publication Year :
- 2008
-
Abstract
- A new strategy (denoted P-SS) for estimating the correct fault zone in distance relays is introduced. The main difference between the P-SS and conventional setting strategies is that the P-SS does not depend on fixed boundaries for backup zones. It depends on exchanging information between local relays in the same station in addition to a command from the remote end relay. With the proposed strategy, zone-1 covers the entire length of the protected line, zone-2 covers the entire length of any next line irrespective of its length, and zone-3 covers the entire length of any line next to zone-2. The governing rules for the proposed strategy are presented. The strategy is examined against a wide range of setting problems of a real part of a high-voltage network with real relay settings. The results confirm that the P-SS achieves the required accurate, sensitive, and selective relay operation. Index Terms--Distance relays, fault zones, pilot schemes, setting problems.