Back to Search
Start Over
Analysis and design of a new active power filter to cancel neutral current harmonics in three-phase four-wire electric distribution systems
- Source :
- IEEE Transactions on Industry Applications. Nov-Dec, 1994, Vol. 30 Issue 6, p1565, 8 p.
- Publication Year :
- 1994
-
Abstract
- Recent surveys of 208/120 V three-phase four-wire electric systems, buildings, and industrial plants with computers and nonlinear loads show excessive currents in the neutral. These neutral currents are fundamentally third harmonic, and their presence is tied to wiring failures, elevating of neutral potentials, transformer overheating, etc. In response to these concerns, this paper proposes a new active power filter scheme to cancel neutral current harmonics. The proposed approach employs a star/delta transformer along with a two-switch PWM-controlled active filter. The closed loop control of the active power filter guarantees cancellation of neutral current harmonics under varying load conditions. The proposed system drastically improves the overall system performance and virtually eliminates transformer overheating due to harmonics. Experimental results from a prototype active power filter confirm the suitability of the proposed approach.
Details
- ISSN :
- 00939994
- Volume :
- 30
- Issue :
- 6
- Database :
- Gale General OneFile
- Journal :
- IEEE Transactions on Industry Applications
- Publication Type :
- Academic Journal
- Accession number :