Back to Search Start Over

The inspection and strength checking of old circular prestressed reinforced concrete pole

Authors :
Hu Yujing
Cao Xianhui
Xie Yi
Feng Chao
Wang Sida
Zhang Wei
Source :
E3S Web of Conferences, Vol 252, p 03033 (2021)
Publication Year :
2021
Publisher :
EDP Sciences, 2021.

Abstract

The capacity expansion of the old transmission lines will lead to an increase in the load level of exsiting prestressed reinforced concrete pole. In this work, the structural parameters of old pole were detected by X-ray imaging technology. The force conditions of the modified concrete pole under the design conditions and actual service conditions were analyzed by Midas/civil. And combined with the calculation of bearing capacity of the circular prestressed reinforced concrete section, the strength checking was conducted. The results showed that X-ray imaging technology can be used to detect the number of steel bars in pole. In addition, the reforming scheme that existing prestressed reinforced concrete poles were used and original LGJ70/10 conductors were replaced with LGJ95/15, still possess considerable safety factor under the actual maximum load conditions.

Subjects

Subjects :
Environmental sciences
GE1-350

Details

Language :
English, French
ISSN :
22671242
Volume :
252
Database :
Directory of Open Access Journals
Journal :
E3S Web of Conferences
Publication Type :
Academic Journal
Accession number :
edsdoj.fbaabbce360244fc95a022285a988426
Document Type :
article
Full Text :
https://doi.org/10.1051/e3sconf/202125203033