Back to Search Start Over

Non-unit protection method for boundary-component-free MTDC systems using normalized backward traveling waves

Authors :
Fan Xie
Le Liu
Zhiguo Hao
Ting Wang
Songhao Yang
Aleksandra Lekić
Marjan Popov
Source :
International Journal of Electrical Power & Energy Systems, Vol 164, Iss , Pp 110370- (2025)
Publication Year :
2025
Publisher :
Elsevier, 2025.

Abstract

The performance of existing protection methods for multi-terminal direct current systems depends on the availability and sizes of boundary components. To overcome the limitation, this paper proposes a non-unit DC line protection method based on the normalized backward traveling waves (BTWs) of the 1-mode voltage. Firstly, traveling wave propagation characteristics are analyzed, and a rationalization approach based on vector fitting is proposed. Next, the analytical expressions of normalized BTWs are derived, with the negative correlation between them and fault distance proved. Then, the derivative-free conjugate gradient algorithm is utilized for amplitude fitting and normalization calculation. Finally, a non-unit protection method using the normalized BTWs is developed. The performance is validated for both electromagnetic transient PSCAD/EMTDC and real-time digital RSCAD/RTDS simulation. The results demonstrate that the proposed method can accurately identify faults with various fault resistances and locations without requiring boundary components and high sampling frequencies, and it is robust against noise disturbances.

Details

Language :
English
ISSN :
01420615
Volume :
164
Issue :
110370-
Database :
Directory of Open Access Journals
Journal :
International Journal of Electrical Power & Energy Systems
Publication Type :
Academic Journal
Accession number :
edsdoj.ba2575889b834f398546972f8f8251d9
Document Type :
article
Full Text :
https://doi.org/10.1016/j.ijepes.2024.110370