Back to Search
Start Over
Experimental and Numerical Investigation of the Internal Temperature of an Oil-Immersed Power Transformer with DOFS
- Source :
- Applied Sciences, Vol 10, Iss 16, p 5718 (2020)
- Publication Year :
- 2020
- Publisher :
- MDPI AG, 2020.
-
Abstract
- To accurately detect and monitor the internal temperature of an operating power transformer, the distributed optical fiber sensor (DOFS) was creatively applied inside an oil-immersed 35 kV transformer through high integration with the winding wire. On the former basis, the power transformer prototype with a completely global internal temperature sensing capability was successfully developed and it was also qualified for power grid operation through the ex-factory type tests. The internal spatially continuous temperature distribution of the operating transformer was then revealed through a heat-run test and the numerical simulation was also applied for further analysis. Hotspots of windings were continuously located and monitored (emerging at about 89%/90% height of low/high voltage winding), which were furtherly compared with the IEC calculation results. This new nondestructive internal sensing method shows a broad application prospect in the electrical equipment field. Also, the revelation of transformer internal distributed temperature can offer a solid reference for both researchers and field operation staff.
Details
- Language :
- English
- ISSN :
- 20763417
- Volume :
- 10
- Issue :
- 16
- Database :
- Directory of Open Access Journals
- Journal :
- Applied Sciences
- Publication Type :
- Academic Journal
- Accession number :
- edsdoj.b10cca211722490ca3d7b7ec4b9998bb
- Document Type :
- article
- Full Text :
- https://doi.org/10.3390/app10165718