Back to Search Start Over

Impedance remodeling control strategy of grid-connected inverter with inertia-damping phase-locked loop under extremely weak grid

Authors :
Youjun Zhu
Jinbin Zhao
Zhiwei Zeng
Ling Mao
Keqing Qu
Source :
International Journal of Electrical Power & Energy Systems, Vol 158, Iss , Pp 109961- (2024)
Publication Year :
2024
Publisher :
Elsevier, 2024.

Abstract

The operation of the grid-connected inverter (GCI) in weak grid conditions presents a risk of instability due to the presence of high grid impedance and the negative impedance effect of the phase-locked loop (PLL). In response to this issue, this paper introduces an impedance remodeling control strategy for the GCI utilizing the inertia-damping phase-locked loop (ID-PLL). Firstly, the proposed ID-PLL exhibits certain inertia and damping properties in comparison to the traditional PLL (T-PLL), resulting in an enhanced phase margin of the GCI system's equivalent output impedance. Consequently, the adaptation range of the grid impedance increases from 12mH (SCR = 3.00) to 24mH (SCR = 1.37). Next, from the perspective of impedance analysis, this study remodels the PLL impedance and inverter control loop impedance, further improving the amplitude and phase margin of the system's output impedance. As a result, the adaptation range of the grid impedance extends to 33mH (SCR = 1.00), and the transition of grid-connected currents becomes smooth and free of overshoot. Finally, the effectiveness of the proposed control strategy is validated through theoretical analysis and experimental verification.

Details

Language :
English
ISSN :
01420615
Volume :
158
Issue :
109961-
Database :
Directory of Open Access Journals
Journal :
International Journal of Electrical Power & Energy Systems
Publication Type :
Academic Journal
Accession number :
edsdoj.9a1fc9ecaeca4ce0875a16fafe445086
Document Type :
article
Full Text :
https://doi.org/10.1016/j.ijepes.2024.109961