MODERNIZATION OF THE COMPLEX TYPE IK-1U FOR MEASURING THE IMPEDANCE OF THE GROUNDING DEVICE OF A LIGHTNING ARRESTER AND SUPPORTS OF TRANSMISSION LINES

Authors :
D. G. Koliushko
S. S. Rudenko
A. V. Plichko
V. I. Shcherbinin
Source :
Electrical engineering & Electromechanics, Iss 3, Pp 55-58 (2019)
Publication Year :
2019
Publisher :
National Technical University "Kharkiv Polytechnic Institute", 2019.

Abstract

Purpose. The creation of a measuring device for determining the impedance of the grounding of lightning arresters and supports of overhead lines under the influence of aperiodic pulses with the parameters 1.2/50 μs, 8/20 μs and 10/350 μs. Methodology. For this purpose, electrical engineering theory, transient modeling software and natural modeling methods are used. Results. The parameters of the electrical circuits of the additional forming unit were determined to create lightning current pulses with parameters of 10/350 μs using the IK-1U measuring complex. According to the simulation results, a layout of the forming unit in the form of an attachment and the IK-1U complex with the upgraded power supply system were created. Oscillograms of the front and pulse duration are obtained. The specified model was tested when performing electromagnetic diagnostics of the state of the RFP for more than 100 operating electrical substations. Originality. The measuring complex IK-1U was improved, which made it possible to determine the impulse impedance of the grounding device of lightning arresters when exposed to a current of 10/350 μs, 8/20 μs and of voltages 1.2/50 μs. Practical value. Upgraded device allows measurements in accordance with modern international requirements.

Details

Language :
English, Russian, Ukrainian
ISSN :
2074272X and 23093404
Issue :
3
Database :
Directory of Open Access Journals
Journal :
Electrical engineering & Electromechanics
Publication Type :
Academic Journal
Accession number :
edsdoj.95b096a724d148e7a1ca82cbd8560b72
Document Type :
article
Full Text :
https://doi.org/10.20998/2074-272X.2019.3.09