Tap Staggering Analysis and Effects on the Adaptive Protection System in Networks With Renewable Energy Sources

Authors :
Hakan Kasap
Mikail Purlu
Belgin Emre Turkay
Reza Ganjavi
Source :
IEEE Access, Vol 11, Pp 138623-138637 (2023)
Publication Year :
2023
Publisher :
IEEE, 2023.

Abstract

Increasing the penetration of renewable energy sources as distributed generation in modern power grids presents several challenges, including voltage level issues and protection system failures resulting from bidirectional power flow and changing network dynamics. Voltage limit violations could potentially damage the utility equipment and lead to power quality problems. Innovative Volt/VAr control methods, such as tap staggering, can be used to overcome these problems. Tap staggering utilizes circulating current between parallel transformers to provide reactive power absorption from the network. However, the absorption of reactive power by the primary substation using tap staggering poses a potential risk to the protection system, particularly the Directional Overcurrent protection scheme with Load Blinder. This could lead to failures or nuisance trips during normal load conditions. In this study, a real power system is modeled using real data in PSS CAPE with 120 scenarios generated through tap staggering application, all based on 24-hour demand/wind generation data. The Tap Staggering Macro and Adaptation Protection Macro were developed for the purpose of analyzing these scenarios. The study demonstrates that tap staggering effectively mitigates overvoltage issues on the transmission system by absorbing reactive power. Although there is an increase in active power losses when tap staggering level is increased on the parallel transformers, the power loss remains within reasonable limits. Despite its benefits, tap staggering has been found to affect the Directional Overcurrent with Load Blinder protection scheme, limiting power transfer generated through wind turbines in the distribution network. This results in changes to the protection scheme’s Directional Overcurrent Pickup, Load Blinder Resistance, and Load Blinder Alpha parameters, requiring adaptation in all scenarios. After adaptation, the protection system operates reliably, guaranteeing efficient and unrestricted transmission of distributed generation power to the grid.

Details

Language :
English
ISSN :
21693536
Volume :
11
Database :
Directory of Open Access Journals
Journal :
IEEE Access
Publication Type :
Academic Journal
Accession number :
edsdoj.669fec25daf54b599c4250cf371d6ded
Document Type :
article
Full Text :
https://doi.org/10.1109/ACCESS.2023.3339782