Back to Search
Start Over
Experimental study on the performance of the vertical shell-tube indirect evaporative cooler with inner grooved tubes
- Source :
- Scientific Reports, Vol 14, Iss 1, Pp 1-10 (2024)
- Publication Year :
- 2024
- Publisher :
- Nature Portfolio, 2024.
-
Abstract
- Abstract The vertical tube indirect evaporative cooler (VTIEC) could be preferred one to air-conditioning buildings if its water film quality could be improved. This paper proposed a new VTIEC with inner grooved tubes to improve the water film quality and obtained its performance by experimental method. The results indicated that inner grooved tubes have positive effects on the water film and performance of the new VTIEC. A low working air enthalpy at inlet can significantly improve the total cooling capacity from evaporation, and then VTIEC performance. In this paper conditions, the velocity ratio of 1.52 of the produced air to the working air is better one condition compared to 1.01 and 2.28. The produced air velocity is positive effect on the cooling capacity per unit area until the produced air velocity of about 4.05 m/s and is negative effect on COP. The maximum unit cooling capacity, wet-bulb efficiency and COP are 307.74W/m2, 81.7% and 44.97.The results will promote the application of the new VTIEC.
Details
- Language :
- English
- ISSN :
- 20452322
- Volume :
- 14
- Issue :
- 1
- Database :
- Directory of Open Access Journals
- Journal :
- Scientific Reports
- Publication Type :
- Academic Journal
- Accession number :
- edsdoj.5996f72bcc7748338e3f6e276696c61d
- Document Type :
- article
- Full Text :