Retrofitting of an air-cooled data center for energy efficiency

Authors :
Mustafa Kuzay
Aras Dogan
Sibel Yilmaz
Oguzhan Herkiloglu
Ali Serdar Atalay
Atilla Cemberci
Cagatay Yilmaz
Ender Demirel
Source :
Case Studies in Thermal Engineering, Vol 36, Iss , Pp 102228- (2022)
Publication Year :
2022
Publisher :
Elsevier, 2022.

Abstract

Small-scale data centers suffering from low cooling efficiency consume an intense power for reliable operation of IT equipment. In this study, thermal distribution in an air-cooled data center is simulated using an open source Computational Fluid Dynamics (CFD) model to examine the underlying mechanism that reduces thermal and cooling efficiencies. The numerical model is validated with the temperature measurements conducted in the data center. Numerical simulations have revealed that recirculating hot flows observed at the top of the racks increased the air temperature beyond the allowable maximum temperature. To this end, the data center has been retrofitted by creating a hot aisle with the implementation of a moving baffle at the rear of the rack. Numerical simulations conducted for two working scenarios have demonstrated that such a minor modification could result in remarkable enhancement in the cooling efficiency. Efficiency of the data center has improved by 47.2% and 22.7% with respect to the RCI (Rack Cooling Index) and RHI (Return Heat Index), respectively. The present numerical model can capture distributions of the efficiency metrics over the racks. Present methodology can be used to reduce power consumption by the cooling and ventilation systems in existing data centers.

Details

Language :
English
ISSN :
2214157X
Volume :
36
Issue :
102228-
Database :
Directory of Open Access Journals
Journal :
Case Studies in Thermal Engineering
Publication Type :
Academic Journal
Accession number :
edsdoj.48918465e53a4ab8b80128b05c05b16f
Document Type :
article
Full Text :
https://doi.org/10.1016/j.csite.2022.102228