Analysis of operating conditions of a cooling installation with carbon dioxide
- Source :
- E3S Web of Conferences, Vol 100, p 00005 (2019)
- Publication Year :
- 2019
- Publisher :
- EDP Sciences, 2019.
-
Abstract
- In response to international regulations, natural refrigerants such as carbon dioxide are more and more frequently used in the refrigeration industry. Due to thermodynamic properties, R-744 is used in the transcritical cycle as an individual refrigerant. In the hereby article, high pressure of CO2 and air temperature values were analysed. The measurements were conducted on the gas cooler side and involved external air temperature values in the summer period between 1 June to 30 September 2018. The “Booster” installation was used in one of Polish supermarkets. Correlations required to determine the optimal pressure of carbon dioxide depending on ambient temperature were presented in the article. The equations presented hereby allowed to maximize the energy efficiency ratio. An optimal high pressure for one of the correlations from literature was calculated on the basis of the measurement of ambient temperature. Actual and optimal pressure values of carbon dioxide were compared in the analysed period of time.
- Subjects :
- Environmental sciences
GE1-350
Subjects
Details
- Language :
- English, French
- ISSN :
- 22671242
- Volume :
- 100
- Database :
- Directory of Open Access Journals
- Journal :
- E3S Web of Conferences
- Publication Type :
- Academic Journal
- Accession number :
- edsdoj.16cf60a12942419789fb063b5b9a3e60
- Document Type :
- article
- Full Text :
- https://doi.org/10.1051/e3sconf/201910000005