Back to Search Start Over

Evaluation of the efficacy of ultraviolet irradiation for disinfection of hospital water contaminated byLegionella

Authors :
Daniela Cabodi
L. Franzin
Cristina Fantino
Source :
Journal of Hospital Infection. 51:269-274
Publication Year :
2002
Publisher :
Elsevier BV, 2002.

Abstract

We evaluated the efficacy of the ultraviolet irradiation on hospital water colonized by Legionella pneumophila serogroup 3, by inserting a lamp system on a hot water pipe supplying a small area. Cultures were performed for four months from 5L samples of water, collected before and after the ultraviolet treatment at the lamp unit and from two distal points. Irradiation was effective immediately after disinfection (