Traceable calibration system for non-conventional current sensors with analogue or digital output

Authors :
Soeren de Rose
Michael Seckelmann
Yeying Chen
Enrico Mohns
Source :
AMPS
Publication Year :
2021
Publisher :
Zenodo, 2021.

Abstract

This paper describes the setup of a traceable calibration system for conventional or non-conventional current sensors even with digital output. The system is lately developed at PTB within the frame of the European project ���FUTUREGRID II���. Details of the system components are presented. The absolute phase errors of the two-channel generator related to the pulse per second time reference of the global positioning system can be configured to almost zero. The accuracies of the reference current transformers are within ��10 ��A/A and ��rad at power frequency. The sampled value receiver box is firstly validated for the sample rate of 4 kHz according to the IEC standard 61869-9 [1].<br />Cite as Y. Chen, E. Mohns, M. Seckelmann and S. de Rose, "Traceable calibration system for non-conventional current sensors with analogue or digital output," 2021 IEEE 11th International Workshop on Applied Measurements for Power Systems (AMPS), 2021, pp. 1-6, doi: 10.1109/AMPS50177.2021.9586012.