Back to Search Start Over

Carrier relaying and rapid reclosing at 110 kv

Authors :
E. C. Stewart
R. E. Powers
G. E. Heberlein
R. E. Pierce
Source :
Electrical Engineering. 55:1120-1129
Publication Year :
1936
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 1936.

Abstract

This paper describes an application of carrier-current relaying combined with rapid reclosure of circuit breakers by means of which the continuity of service to a large industrial load supplied by a long single-circuit line was improved. A 110-kv line 120 miles long, forming part of an interconnected loop, has been equipped in this way to clear faults and restore service in approximately one second. The effect of the connected motor load on circuit interruption is also discussed.

Details

ISSN :
00959197
Volume :
55
Database :
OpenAIRE
Journal :
Electrical Engineering
Accession number :