Voltage Reduction in Medium Voltage Distribution Systems Using Constant Power Factor Control of PV PCS

Authors :
Junpei Motoyama
Daisuke Iioka
Tsuyoshi Harimoto
Toshio Tanaka
Takahiro Fujii
Source :
Energies; Volume 13; Issue 20; Pages: 5430, Energies, Vol 13, Iss 5430, p 5430 (2020)
Publication Year :
2020
Publisher :
Multidisciplinary Digital Publishing Institute, 2020.

Abstract

Reverse power flow from a photovoltaic (PV) system in a distribution system causes a voltage rise. A relative study regarding the reduction in the distribution feeder voltage depending on system conditions and the magnitude of reverse power flow has been conducted. Several methods for mitigating voltage rise have been proposed; however, the influence of these methods on the voltage in the distribution system, where the voltage is reduced due to reverse power flow, remains to be determined. In this study, the effect of constant power factor control in low-voltage PV systems, which are widely used as voltage rise countermeasures in distribution systems, was analyzed under the condition that the distribution line voltage decreases due to reverse power flow. Consequently, the constant power factor control of the low-voltage distribution system was found to adversely reduce voltage in the medium voltage distribution system due to the consumption of lagging reactive power by the PV systems.