Back to Search
Start Over
Implementation and Performance Evaluation of a Reclosing Method for Shunt Reactor-Compensated Transmission Lines
- Source :
- IEEE Transactions on Power Delivery. 26:954-962
- Publication Year :
- 2011
- Publisher :
- Institute of Electrical and Electronics Engineers (IEEE), 2011.
-
Abstract
- This paper proposes a new control method to reduce overvoltages due to three-phase reclosing for shunt compensated transmission lines (TL). The method detects the first minimum voltage region of the beating across the circuit breakers after protection dead time and works independently of voltage zero crossing, reducing significantly the reclosure time. The controller was tested on a Real Time Digital Simulator (RTDS) and its performance was compared to the traditional preinsertion resistor approach and another existing control method.
- Subjects :
- Engineering
business.industry
Energy Engineering and Power Technology
Dead time
Zero crossing
law.invention
Electric power transmission
Overvoltage
law
Control theory
Real Time Digital Simulator
Electronic engineering
Electrical and Electronic Engineering
Resistor
business
Shunt (electrical)
Circuit breaker
Voltage
Subjects
Details
- ISSN :
- 19374208 and 08858977
- Volume :
- 26
- Database :
- OpenAIRE
- Journal :
- IEEE Transactions on Power Delivery
- Accession number :
- edsair.doi.dedup.....71c6885796f6d4717440a2bf1a7644e3
- Full Text :
- https://doi.org/10.1109/tpwrd.2010.2084111