Back to Search
Start Over
Influence of ring main units and substations on online partial-discharge detection and location in medium-voltage cable networks
- Source :
- IEEE Transactions on Power Delivery, 26(2), 1064-1071. Institute of Electrical and Electronics Engineers
- Publication Year :
- 2011
-
Abstract
- Online partial-discharge (PD) monitoring of medium-voltage power cables is traditionally performed on a cable between two consecutive ring main units (RMUs). PD location is achieved using a sensor at each cable end. Monitoring multiple consecutive cables, with RMUs in between, using a single monitoring system is more efficient. In addition, substations and RMUs without possibilities for sensor installation can be circumvented by installing the sensor at the next RMU. This paper studies how RMUs and substations along the cable under test affect online monitoring, including their influence on detection sensitivity, location accuracy, and charge estimate accuracy. Single-sided PD measurement, including PD location, with an RMU or substation at the far end is also considered. Models for RMUs and substations are proposed and verified by measurements. The performance of online PD monitoring is studied for a number of network configurations.
- Subjects :
- Engineering
business.industry
Electrical engineering
Energy Engineering and Power Technology
Condition monitoring
Ring circuit
Power (physics)
Installation
Partial discharge
Electronic engineering
Sensitivity (control systems)
Electrical and Electronic Engineering
business
Electrical impedance
Voltage
Subjects
Details
- Language :
- English
- ISSN :
- 08858977
- Volume :
- 26
- Issue :
- 2
- Database :
- OpenAIRE
- Journal :
- IEEE Transactions on Power Delivery
- Accession number :
- edsair.doi.dedup.....41809c7d9287dfdd0749a7ebf83dffd4
- Full Text :
- https://doi.org/10.1109/tpwrd.2010.2089808