Sensitivity Analysis of Evaporative Condensers Performance Using an Experimental Approach
- Source :
- Energy Procedia. 126:345-352
- Publication Year :
- 2017
- Publisher :
- Elsevier BV, 2017.
-
Abstract
- The evaporative condensers operate at lower condensing temperatures with respect to dry condensing units and involve reduced water consumption if compared with water cooled condensers. A test rig to investigate the evaporative condenser at small scale has been designed and built up. The condensing refrigerant has been simulated by electrical heaters and an air handling unit provides air with dry bulb temperature and relative humidity set by the user. All the c affecting the evaporative condenser performance can be monitored and adjusted, in order to carry out either an extensive experimental campaign or a sensitivity analysis. The results, as expected, clearly show that the heat released to air increases with the outer surface temperature of electrical heaters and decreases with relative humidity. An increase of 37.5% of the air flow rate (at constant sprayed water) leads to a maximum reduction of the heat transfer rate of 50%. Different tubes arrangements have been compared, showing as a decrease of the transversal pitch involves worse performance.
- Subjects :
- Engineering drawing
Test bench
Energy
Materials science
Dry-bulb temperature
020209 energy
Heat rejection
02 engineering and technology
Mechanics
Water consumption
Refrigerant
020401 chemical engineering
Experimental test
Sensitivity analysi
Heat transfer
0202 electrical engineering, electronic engineering, information engineering
Relative humidity
0204 chemical engineering
Sensitivity (electronics)
Condenser (heat transfer)
Evaporative condenser
Subjects
Details
- ISSN :
- 18766102
- Volume :
- 126
- Database :
- OpenAIRE
- Journal :
- Energy Procedia
- Accession number :
- edsair.doi.dedup.....0e92b124a2791f77d03e6d9e9b64937e
- Full Text :
- https://doi.org/10.1016/j.egypro.2017.08.232