Back to Search
Start Over
Critical heat flux characteristics of R1234yf, R1234ze(E) and R134a during saturated flow boiling in narrow high aspect ratio microchannels
- Source :
- Kærn, M R, Criscuolo, G, Meyer, K E & Markussen, W B 2021, ' Critical heat flux characteristics of R1234yf, R1234ze(E) and R134a during saturated flow boiling in narrow high aspect ratio microchannels ', International Journal of Heat and Mass Transfer, vol. 180, 121840 . https://doi.org/10.1016/j.ijheatmasstransfer.2021.121840
- Publication Year :
- 2021
- Publisher :
- Elsevier BV, 2021.
-
Abstract
- This experimental study investigated narrow and high aspect ratio multi-microchannels that were micro-machined in copper with thin separating walls during saturated flow boiling of refrigerants. The hypothesis was that these channels could increase the footprint critical heat flux and support the future development of thermal management systems for power electronics and other electronic packages. The measured footprint critical heat flux was as high as 678.5 W/cm2, which is twice as high as other investigations in the literature concerning saturated flow boiling of refrigerants. Two test samples were fabricated with a footprint area of (10 × 10) mm. The first had 25 rectangular channels (198 μm wide, 1167 μm high). The second had 17 rectangular channels (293 μm wide, 1176 μm high). The experimental investigation covered low-GWP replacement refrigerants (R1234yf, R1234ze(E)) as well as the well-examined R134a serving as a benchmark. A large data bank was obtained with 432 data points covering a wide range of typical inlet subcooling (1.3–14.7) K and mass fluxes (333–1260) kg/m2s as well as two nominal saturation temperatures (30 and 40) °C.The effect of inlet subcooling was found to be consistently significant at the higher mass fluxes. This was contradictory to other investigations that found moderate or insignificant effects. The result is suggested to be attributed to the two-phase stability induced by the upstream throttle valve, inlet orifices, isolated refrigerant in the inlet and outlet plenums as well as the short heated length causing higher importance of orifice to channel pressure drop importance. Finally, a new modified Katto and Ohno correlation including the effect of subcooling was proposed, achieving a 4.0% mean average error and predicting 93.3% of the data points within 10% error.
- Subjects :
- Fluid Flow and Transfer Processes
Pressure drop
geography
Materials science
geography.geographical_feature_category
Critical heat flux
Mechanical Engineering
Mechanics
Condensed Matter Physics
Inlet
Refrigerant
Subcooling
Microchannels
Electronics cooling
Boiling
Low-GWP refrigerant
Flow boiling
Body orifice
Subjects
Details
- ISSN :
- 00179310
- Volume :
- 180
- Database :
- OpenAIRE
- Journal :
- International Journal of Heat and Mass Transfer
- Accession number :