Back to Search Start Over

Field measurement on the particle concentrations and exposures in five residential buildings in Korea

Authors :
Hyungkeun Kim
Taeyeon Kim
Kyungmo Kang
Yun Gyu Lee
Source :
IOP Conference Series: Materials Science and Engineering. 609:042105
Publication Year :
2019
Publisher :
IOP Publishing, 2019.

Abstract

This study measured five apartments in the Daejeon. There is higher fluctuation for ambient air particle conditions. The average PN (particle number) concentrations was 5.2x108/m3. There are differences between five sites because of fluctuation for ambient air conditions. Particle concentration has different each occupant schedule. I/O ratios were different by occupancy schedules. Indoor particles exceeded 0.7 μm was significant emitted indoor activities. This result comes from two reasons. 1) Penetration by envelopes. 2) Indoor sources by occupants’ activities. PN decay rate (a+k) were 0.49-4.29 h−1 during indoor peak events. Total emitted particles (σ) was 0.0136.15 x 1013 particles per events. The cooking generated PN were wide range because of different event conditions. The ventilation rate is not enough to remove particles.

Details

ISSN :
1757899X and 17578981
Volume :
609
Database :
OpenAIRE
Journal :
IOP Conference Series: Materials Science and Engineering
Accession number :
edsair.doi...........fc13d0bc04bcfed345667485e3cd778e
Full Text :
https://doi.org/10.1088/1757-899x/609/4/042105