Back to Search Start Over

Study on the influence of amorphous debris on the electric field of amorphous alloy transformer in urban rail transit

Authors :
Dongni Shi
Yuhan Zhao
Jiannan Zheng
Xiaodan Qin
Zhiyuan Zhang
Source :
2017 IEEE Transportation Electrification Conference and Expo, Asia-Pacific (ITEC Asia-Pacific).
Publication Year :
2017
Publisher :
IEEE, 2017.

Abstract

In order to improve the efficiency of the power system, in recent years, China has been actively promoting the use of energy-saving amorphous alloy transformer. As the oil- immersed amorphous alloy distribution transformer is the fully sealed and maintenance-free transformer, iron core debris of amorphous alloy once produced will accumulate and this will result in great harm on the insulation and stability of the amorphous alloy transformer. This article uses the finite element analysis for the study of distribution characteristics of amorphous alloy iron core debris and the impact of electromagnetic performance of the oil-immersed amorphous alloy transformer. The electric field internal the amorphous alloy core debris is zero, and the electric field around it becomes three times larger. Amorphous debris cause uneven distribution of electric field in the oil, which will easily lead to insulating oil breakdown.

Details

Database :
OpenAIRE
Journal :
2017 IEEE Transportation Electrification Conference and Expo, Asia-Pacific (ITEC Asia-Pacific)
Accession number :
edsair.doi...........f6444dcc35f8e15d0fa85e72d4017688
Full Text :
https://doi.org/10.1109/itec-ap.2017.8081042