Abstract
- This paper presents simplified formulas and curves for rapid and accurate evaluation of steady-state and transient performance of a-c generators. The calculations provide for the determination of no-load, zero-power-factor and full-load field current, short-circuit ratio, leakage reactance, synchronous reactance, transient reactance, substransient reactance, transient open-circuit and short-circuit time constants, and d-c time constant. A simple formula is proposed for rough approximation of no-load core loss. These formulas and curves apply to very small machines with semi-enclosed slots, very short air gaps and high flux densities in the iron, as well as to the larger machines covered by previous papers on this subject.
- Subjects :
- Engineering
Leakage inductance
Steady state
Field (physics)
business.industry
Mathematical analysis
Reactance
Time constant
Industrial and Manufacturing Engineering
Magnetic flux
Shock absorber
Control and Systems Engineering
Condensed Matter::Superconductivity
Electronic engineering
Transient (oscillation)
Electrical and Electronic Engineering
business
Subjects
Details
- ISSN :
- 00963860
- Volume :
- 69
- Database :
- OpenAIRE
- Journal :
- Transactions of the American Institute of Electrical Engineers
- Accession number :
- edsair.doi...........f4d720737b4d5e1574e07c10c43f1319
- Full Text :
- https://doi.org/10.1109/t-aiee.1950.5060290