Considerations on the coordinated control of controllable reactors

Authors :
Z.D. Yin
Z.Q. Wang
L.X. Zhou
X.N. Xiao
Y.T. Tan
Z.J. Wang
Source :
2008 5th International Conference on the European Electricity Market.
Publication Year :
2008
Publisher :
IEEE, 2008.

Abstract

In the extra-high voltage long transmission line, the non-allowed increasing of power voltage and the corresponding transient oscillation over-voltage are often occurred. The continued burning of the secondary arc usually keeps quite a long time for the high voltage level, long line and large capacity. There must lead to the failure of the re-closing if the secondary arc is not extinguished promptly, which will affect the security and stability of the system. In this paper, the dynamic induced over-voltage model as well as the dynamic secondary arc model in single-phase asymmetric breaking is established based on the distribution parameters of EHV long-line. A novel kind of high-controlled shunt reactor with a small reactor in the neutral is adopted to suppress the transient oscillation over-voltage and the secondary arc. Since the neutral point small reactor is constrained by the positive-sequence and zero-sequence capacitance of the line and the shunt reactor as well. The coordinate control of the neutral controllable small reactor achieves the dynamic change in accordance with the high-controlled shunt reactor which can realize the compensation of the phase capacitor so as to suppress the induced over-voltage and the secondary arc effectively.

Details

Database :
OpenAIRE
Journal :
2008 5th International Conference on the European Electricity Market
Accession number :
edsair.doi...........f38e2f1bce156109fc8a8463c36f6f13
Full Text :
https://doi.org/10.1109/eem.2008.4579080