New Fault Impedance Computations for Unsynchronized Two-Terminal Fault-Location Computations

Authors :
Chi-Shan Yu
Li-Ren Chang
Jr-Ru Cho
Source :
IEEE Transactions on Power Delivery. 26:2879-2881
Publication Year :
2011
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2011.

Abstract

This letter proposes new fault impedance computations for a two-terminal transmission line. Only unsynchronized two-terminal measurements are required when using the proposed equations. The fault location can be obtained by using a pure resistance assumption after computing the fault impedance. The proposed equations are very suitable for an unsynchronized fault-location problem. This study used a MATLAB/SIMULINK simulator to show the effectiveness of the proposed equations.