Electronic Frequency Converter Feeding Single-Phase Circuit and Controlling Feeder Voltage With Fixed Power Factor Method for Shinkansen

Authors :
K. Kunomura
Midori Otsuki
M. Onishi
M. Kai
Yoshinori Tsuruma
Naotaka Iio
N. Nakajima
Source :
IEEE Transactions on Power Electronics. 27:3888-3896
Publication Year :
2012
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2012.

Abstract

In the Tokaido Shinkansen, the instantaneous feeding power of substations has increased because of the high-density train schedule and the improved acceleration performance of the rolling stock. If the load power of feeding substations increases any further, it will not be possible to maintain the feeder voltage when the power converter supplies only reactive power. In consideration of such a situation in the frequency conversion section, an electronic frequency converter that controls the ac voltage using a fixed power factor method was developed. The superiority of the proposed control method is confirmed with electromagnetic transient program calculations and field test results. The electronic frequency converter has been in operation since February 2009 with good performance, showing the success of the system development described in this paper.