Back to Search Start Over

Non‐communication protection scheme for power transmission system based on transient currents, HHT and SVM

Authors :
Zhenwei Guo
Shengjie Yang
YongBo Sui
WenXin Yu
Lieping Zhang
Zhixian Zhong
Source :
IET Generation, Transmission & Distribution. 12:2816-2824
Publication Year :
2018
Publisher :
Institution of Engineering and Technology (IET), 2018.

Abstract

How to improve the reliability has been a challenging task for transient protection, which has been affected seriously by the fault initial angle (FIA) and transient resistance (TR). Based on support vector machine (SVM), a novel smart transient protection method is presented in this study, which protects a bus and two transmission lines connected to the bus. The method is based on the measurements from the two close-in ends of the two lines. Hilbert–Huang transform is used to extracting instantaneous amplitude from the measured currents. The fault area is determined from the two instantaneous amplitude-integral (IA) of the transient fault currents, the difference of the two IAs, FIA, and the TR. SVM is utilised to determine the fault area. Two IAIs, difference of IAs, FIA and TR are treated as the input to SVMs. Faults with different FIA and TR are treated as a different class of fault, respectively. Correspondingly, a different criterion of discrimination is automatically employed by SVMs for a different fault class. The influence of FIA and TR is eliminated significantly, and the reliability of protection is enhanced substantially. The performance of the method is tested using ATP/EMTP with satisfactory results.

Details

ISSN :
17518695
Volume :
12
Database :
OpenAIRE
Journal :
IET Generation, Transmission & Distribution
Accession number :
edsair.doi...........ebe61a9d7af014b9727227ef262d2891
Full Text :
https://doi.org/10.1049/iet-gtd.2017.0862