3-D Assessment of Human Hazard by Outdoor Electrical Facilities in Submerged Area

Authors :
Tae-Hyun Ha
Ji-In Lee
Dae-Kyeoog Kim
Yoon-Cheol Ha
Hyuo-Goo Lee
Jeong-Hyo Bae
Source :
IFAC Proceedings Volumes. 36:957-962
Publication Year :
2003
Publisher :
Elsevier BV, 2003.

Abstract

In this paper, we show three-dimensional distribution of voltages resulted from the leakage current originated from outdoor electrical facilities in a submerged area. In case these facilities are grounded by the neutral line mUltiple grounding method, the existence of ungrounded electrical facilities can cause a disastrous effect on near-by passengers. In order to investigate this situation, we installed a real-scale test field for the experiment type I (for the leakage current path between a enclosure grounded electrical facility and another enclosure grounded one), and that for the experiment type 11 (for the leakage current path between a enclosure grounded electrical facility and another ungrounded one). For both cases, we carried out three-dimensional monitoring of the voltage distribution while varying additional conditions such as the exposure of the underground cables and the fmishing of cable connection part. The result shows that a disastrous effect on human safety can arise from the leakage current without a pertinent measure for the construction and maintenance of outdoor electrical facilities.