Back to Search
Start Over
Instant current limiter using a magnetic switching for DC circuit — Basic principles and circuit analysis
- Source :
- 2009 Transmission & Distribution Conference & Exposition: Asia and Pacific.
- Publication Year :
- 2009
- Publisher :
- IEEE, 2009.
-
Abstract
- In this paper, instant current limiter using a Magnetic Switching for DC power system is proposed. In DC power system, it is very difficult to cut off the fault current because it has no Zero-Crossing. This paper proposes an instant current limiter to reduce the DC current instantaneously by using a magnetic switching circuit, which can be utilized as a DC FCL(Fault Current Limiter) for DC circuit breaker. The existing cut-off approach for DC system uses dI/dt to decide whether the fault occurs or not in order to achieve fast cut-off approach before the fault current is increased. But fast fault decision using dI/dt has a relatively large uncertainty so it would cause malfunctions. With the aid of the proposed FCL, it is possible to achieve a safe cut-off of the fault current after the fault current is increased enough. We can ensure an enough time to decide the fault occurrence and reduce a cut-off capacity and increase a safety to cut off the fault current. The suggested system can also be utilized to AC current limiter for power systems with a large range of application in the future.
Details
- Database :
- OpenAIRE
- Journal :
- 2009 Transmission & Distribution Conference & Exposition: Asia and Pacific
- Accession number :
- edsair.doi...........e73719514f93582a4387a441ff8c7a69
- Full Text :
- https://doi.org/10.1109/td-asia.2009.5357023