Back to Search Start Over

Study on Typical Diversion Structures and Fault of 220kV Cable-Conductor Bushings

Authors :
Jian Sheng Li
Yi Ming Wu
Chao Yu
Yun Cai Lu
Peng Wu
Na Xue
Source :
Advanced Materials Research. :1066-1070
Publication Year :
2014
Publisher :
Trans Tech Publications, Ltd., 2014.

Abstract

According to a TOM bushing faults, three typical 220kV cable-conductor bushings (COT, TOM and BRDLW) widely used in the power grid are analyzed about diversion structure. Bushing diversion structure, diversion contact surface, current path and installation sensitivity are discussed in the paper. The study found that installation accuracy of TOM bushing has greater effect on contact resistance of diversion path than others. The improper installation of TOM bushing caused overheating defects and finally developed into this bushing fault.

Details

ISSN :
16628985
Database :
OpenAIRE
Journal :
Advanced Materials Research
Accession number :
edsair.doi...........d697606c68a84687704ced155e15493c
Full Text :
https://doi.org/10.4028/www.scientific.net/amr.1070-1072.1066