Back to Search
Start Over
Arc Shape and Arc Temperature Measurements in SF6 High-Voltage Circuit Breakers Using a Transparent Nozzle
- Source :
- IEEE Transactions on Plasma Science. 46:2120-2125
- Publication Year :
- 2018
- Publisher :
- Institute of Electrical and Electronics Engineers (IEEE), 2018.
-
Abstract
- An investigation was performed to measure the arc temperature and arc shape in a SF6 circuit breaker (CB) during large current interruption. Experiments were conducted with a 126-kV SF6 CB. To measure the arc shape and the spatial distribution of the arc temperature effectively, the nozzle was replaced with a transparent organic glass material made from a polytetrafluoroethylene material. The arc shape variation was captured by a high-speed camera, and optical filters were installed on the camera in the case of overexposure. The arc temperature measurement was performed by obtaining the spectral line intensities of Cu I 510.5, Cu I 515.3, and Cu I 521.8 nm through a spectrograph, and the temperature was calculated by the two-line method. Measurements were performed during the entire operating process. The variations in the arc temperature with operating time were obtained. The established method was effective for measuring variations in the arc shape and temperature throughout the entire operating process.
- Subjects :
- 010302 applied physics
Nuclear and High Energy Physics
Materials science
business.industry
Nozzle
High voltage
Condensed Matter Physics
01 natural sciences
Temperature measurement
010305 fluids & plasmas
Sulfur hexafluoride
Arc (geometry)
chemistry.chemical_compound
Optics
chemistry
0103 physical sciences
Optical filter
business
Spectrograph
Circuit breaker
Subjects
Details
- ISSN :
- 19399375 and 00933813
- Volume :
- 46
- Database :
- OpenAIRE
- Journal :
- IEEE Transactions on Plasma Science
- Accession number :
- edsair.doi...........cfd56e22121574e48cd1bde13ed5ae5a
- Full Text :
- https://doi.org/10.1109/tps.2018.2834735