Frequency Response of Oil Impregnated Pressboard and Paper Samples for Estimating Moisture in Transformer Insulation

Authors :
Stanislaw Gubanski
Chandima Ekanayake
A. Graczkowski
Krzysztof Walczak
Source :
IEEE Transactions on Power Delivery. 21:1309-1317
Publication Year :
2006
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2006.

Abstract

Knowledge about moisture content in oil impregnated paper insulation is essential when estimating remaining lifetime of power transformers. Direct evaluation of moisture content is rarely possible due to inaccessibility of the internal insulation system in transformers. Therefore, various indirect estimation techniques are utilized. Frequency domain spectroscopy (FDS) measurements of transformer insulation belong to this group. To perform high quality interpretation of results of FDS measurements a good knowledge on dielectric responses in oil impregnated pressboard and paper is required, especially as it refers to their variation with water content and temperature. The aim of this paper is to provide an open access to the frequency domain spectra of oil impregnated paper and pressboard samples, which can then be used in modeling of the results of diagnostic measurements in power transformers.