Back to Search Start Over

An Analytical Model for Frequency Nadir Prediction Following a Major Disturbance

Authors :
Kerui Wen
Cuicui Jin
Liu Liu
Weidong Li
Jiakai Shen
Yu Ba
Source :
IEEE Transactions on Power Systems. 35:2527-2536
Publication Year :
2020
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2020.

Abstract

The frequency nadir is a significant indicator for the primary frequency response monitoring and control. It is imperative to predict the maximum frequency deviation and the time at which the maximum occurs with high efficiency and accuracy following a major disturbance. To develop an analytical model for the frequency nadir prediction, the closed-loop is broken and a parabolic frequency deviation is input for decoupling the calculation of governor response and frequency deviation. Following which, the polynomial fitting is adopted to depict the primary frequency response characteristic of each governor. The iterative numerical solution for the frequency nadir prediction model is carried out based on the insight into the features of governor response. Case studies are presented to verify the performance of the analytical model over WSCC 9-bus system, New England 39-bus system and practical provincial power system, where the frequency nadir prediction model demonstrates its advantages of easy implementation, minimum computation, and high accuracy.