Back to Search Start Over

Fuzzy logic based extended integral control for load frequency control

Authors :
Heon-Su Ryu
Baik Kim
Seog-Joo Kim
Sung-Chul Park
Young-Hyun Moon
Source :
2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194).
Publication Year :
2002
Publisher :
IEEE, 2002.

Abstract

This study presents an application of fuzzy logic based method to determine the optimal parameters for the extended integral control scheme. The performance of the extended integral control is greatly dependent on the decaying factor. For an optimal or near optimal performance, it is necessary that the decaying factor as well as the feedback gains should be changed very quickly in response to changes in the system dynamics. However, because of its time-varing characteristic, the optimal decaying factor is difficult to be selected analytically. By adopting fuzzy set theory, the decaying factor can be determined quickly to respond to the variation of the feedback signals. This study builds a fuzzy rule base with use of the change of frequency and its rate as inputs. A set of decision rules is established to relate input signals to the decaying factor. The computer simulation has been conducted for the single machine system. The simulation results show that the proposed fuzzy logic based controller yields more improved control performance than the conventional PI controller.

Details

Database :
OpenAIRE
Journal :
2001 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.01CH37194)
Accession number :
edsair.doi...........b32ed82965024800e49c47b8157bcf65
Full Text :
https://doi.org/10.1109/pesw.2001.917263