Back to Search Start Over

Development of the double-rod-type jumper horns in strain assemblies with pipe jumpers for 500-kv transmission lines

Authors :
Tadashi Amakawa
Sakae Kimura
Masatoyo Shibuya
Kiyoshi Sano
Source :
Electrical Engineering in Japan. 113:52-60
Publication Year :
1993
Publisher :
Wiley, 1993.

Abstract

This paper proposes double-rod-type jumper horns in strain assemblies with pipe jumpers for 500-kV transmission lines, the structure of which is very simple. It can be estimated that no corona discharge appears on the horns under the line voltage of 525 kV. The arc behavior on the double-rod-type jumper horns is similar to that on the single-rod-type horns. The arc can be held stably for 60 ms against strong wind (10 m/s). The stable duration increases more than 300 ms under windless condition, therefore the horns have been adopted for practical use.

Details

ISSN :
15206416 and 04247760
Volume :
113
Database :
OpenAIRE
Journal :
Electrical Engineering in Japan
Accession number :
edsair.doi...........9d09052dc2e79e2f8d3a7c9b34efa87d
Full Text :
https://doi.org/10.1002/eej.4391130705