Back to Search Start Over

Optimum thermodynamic performance of three-stage refrigerating systems

Authors :
M Prasad
V.K Gupta
Source :
International Journal of Refrigeration. 6:103-107
Publication Year :
1983
Publisher :
Elsevier BV, 1983.

Abstract

The refrigeration efficiency, mass flows through IP and HP compressors, power input and inter-stage pressures at the optimum thermodynamic performance of three stage systems are presented graphically for the most common refrigerants, R 12, R 22 and R 717. Correlations are developed to account for the effects of subcoooing of condensate and super-heating of vapour in the evaporator, each up to 15 K. The effects of superheat up to 4 K for the vapours entering the IP and HP compressors on the system performance are also studied in order to simulate real systems more closely. The respective ranges of condensing and evaporating temperatures are taken as 273.15 to 333.15 K and 273.15 to 213.15 K, with T h − T 1 ⩾60 K.

Details

ISSN :
01407007
Volume :
6
Database :
OpenAIRE
Journal :
International Journal of Refrigeration
Accession number :