Back to Search Start Over

Partial discharges at a triple junction metal/solid insulator/gas and simulation of inception voltage

Authors :
Lucian Caliap
Nelly Bonifaci
André Denat
C. Tran Duy
P. Ponchon
Olivier Lesaint
Alain Girodet
B. Gelloz
Source :
Journal of Electrostatics. 66:319-327
Publication Year :
2008
Publisher :
Elsevier BV, 2008.

Abstract

In gas-insulated systems, the presence of solid insulators used to hold conductors at high voltage induces the presence of triple interfaces where the metal, solid insulator and gas are in contact. These regions, usually named “triple junction”, constitute weak points for the insulation, mainly due to the mismatch between permittivities of solid and gas, which induces an enhancement of the electric field. If the design of these regions is not carried out with great care, partial discharges (PDs) may appear and accelerate the ageing of the insulator. This paper deals with an experimental study of PDs in a “triple junction” electrode configuration, carried out with sensitive electrical and optical PD measurements. Experiments are done in two pure gases, nitrogen and SF6. Two discharge regimes can be observed: very small discharges (

Details

ISSN :
03043886
Volume :
66
Database :
OpenAIRE
Journal :
Journal of Electrostatics
Accession number :
edsair.doi...........8145d5408baa01c568f5fad0c9bf57f5
Full Text :
https://doi.org/10.1016/j.elstat.2008.01.011