Comparison Test and its Evaluation of Flowmeters for Heat Meter

Authors :
Hae-Man Choi
Yong-Moon Choi
Byung-Ro Yoon
M. A. Wahid
S. Samion
N. A. C. Sidik
J. M. Sheriff
Source :
AIP Conference Proceedings.
Publication Year :
2010
Publisher :
AIP, 2010.

Abstract

This study selected a total of 24 heat flowmeters consisting of three types: impeller, electromagnetic and ultrasonic, 8 meters each. The diameter was 0.05 m (9 meters), 0.08 m (9 meters), and 0.15 m (6 meters). In accordance with the OIML R 75 testing method accuracy, installation position, external environment, and durability were tested, and the flowmeter property field test was conducted in the field where of heat supply from winter to summer in order to select the type of heat flowmeter best suited for the circumstances in Korea. According to the test result, all 3 types of flowmeters met the OIML Recommendation, but the result of the field test showed that the electromagnetic flowmeters displayed a deviation at the low flow rate during summer. The impeller flowmeters showed accuracy suggested by the OIML Recommendation, but the ultrasonic flowmeter, a next‐generation flowmeter, which is strong against contamination, low in maintenance‐rate, and high in accuracy as it has no moving part, was found to be the best choice.