Back to Search
Start Over
Countermeasure to Prevent the Incorrect Blocking of Differential Protection Applied to Converter Transformers
- Source :
- IEEE Transactions on Power Delivery. 35:95-105
- Publication Year :
- 2020
- Publisher :
- Institute of Electrical and Electronics Engineers (IEEE), 2020.
-
Abstract
- Harmonic blocking is usually applied by converter transformer differential protection to prevent protection mal-operation during an inrush condition, but it may incorrectly block the protection during an internal fault. This paper first makes an in-depth analysis on factors that lead to differential protection failure to trip for converter transformer internal faults. The main factor responsible for the protection failure to trip is half-cycle saturation of the converter transformer core, which results from the dc component in the fault current. This suggests that harmonic blocking may not be suitable for differential protection of converter transformers to identify inrush conditions. In this regard, this paper proposes a novel method using mathematical morphology to effectively discriminate between the conditions caused by inrush and internal faults. This method implements the waveform symmetry criterion and improved morphological gradient criterion to distinguish between these two conditions. The effectiveness of the proposed method is evaluated based on extensive simulation, and the presented results show that the proposed method can ensure operation for all types of internal faults. Additionally, this method improves the accuracy of inrush identification, even in extreme cases, such as sympathetic inrush and inrush with current transformer saturation.
- Subjects :
- Morphological gradient
Computer science
020209 energy
Energy Engineering and Power Technology
02 engineering and technology
Fault (power engineering)
Inrush current
Current transformer
law.invention
Harmonic analysis
Control theory
law
0202 electrical engineering, electronic engineering, information engineering
Waveform
Electrical and Electronic Engineering
Transformer
DC bias
Subjects
Details
- ISSN :
- 19374208 and 08858977
- Volume :
- 35
- Database :
- OpenAIRE
- Journal :
- IEEE Transactions on Power Delivery
- Accession number :
- edsair.doi...........7819de62fd4b155ed3deab37a59df54f