Back to Search Start Over

Operation and performance of a medium-voltage DC link

Authors :
Avinash Aithal
Jianzhong Wu
Source :
CIRED - Open Access Proceedings Journal. 2017:1355-1358
Publication Year :
2017
Publisher :
Institution of Engineering and Technology (IET), 2017.

Abstract

The operation of a voltage source converter (VSC)-based medium-voltage (MV) direct current (DC) link is described. The use of a DC link in an MV distribution network is presented, considering salient similarities and differences to a high-voltage DC link. A PSCAD/EMTDC model was used to demonstrate the dynamic operation of an MVDC link, under normal and faulted network conditions. The study shows that MVDC can provide flexibility in a distribution network by decoupling real (P) and reactive (Q) power flows through the link, under normal operation. During a fault, however, the current injected from the converter could interfere with the detection and discrimination of AC system faults, in distribution networks with current-based protection scheme.

Details

ISSN :
25150855
Volume :
2017
Database :
OpenAIRE
Journal :
CIRED - Open Access Proceedings Journal
Accession number :
edsair.doi...........5e36ef5976d6ff5520720beff1a6e54d