Operation and performance of a medium-voltage DC link
- Source :
- CIRED - Open Access Proceedings Journal. 2017:1355-1358
- Publication Year :
- 2017
- Publisher :
- Institution of Engineering and Technology (IET), 2017.
-
Abstract
- The operation of a voltage source converter (VSC)-based medium-voltage (MV) direct current (DC) link is described. The use of a DC link in an MV distribution network is presented, considering salient similarities and differences to a high-voltage DC link. A PSCAD/EMTDC model was used to demonstrate the dynamic operation of an MVDC link, under normal and faulted network conditions. The study shows that MVDC can provide flexibility in a distribution network by decoupling real (P) and reactive (Q) power flows through the link, under normal operation. During a fault, however, the current injected from the converter could interfere with the detection and discrimination of AC system faults, in distribution networks with current-based protection scheme.
Details
- ISSN :
- 25150855
- Volume :
- 2017
- Database :
- OpenAIRE
- Journal :
- CIRED - Open Access Proceedings Journal
- Accession number :
- edsair.doi...........5e36ef5976d6ff5520720beff1a6e54d