Loss Analysis and Efficiency Test of a 3 MW 10 kV AC to ±750 V DC Power Electronic Transformer
- Source :
- 2020 IEEE 9th International Power Electronics and Motion Control Conference (IPEMC2020-ECCE Asia).
- Publication Year :
- 2020
- Publisher :
- IEEE, 2020.
-
Abstract
- In this paper, a 3 MW 10 kV AC to ±750 V DC power electronic transformer (PET) based on cascaded H-bridge (CHB) and isolated series resonant dual active bridge (SRDAB) converters is introduced first. Power losses are analyzed for this PET, including the hard-switching CHB, the soft-switching SRDAB and the medium-frequency isolation transformer (MFT). The results show that the losses of this PET is not only dependent of the input power but also dependent of the power flow direction. The field efficiency measurement results of the 3 MW 10 kV AC to ±750 V DC PET proved the correctness and accuracy of the loss analysis and the power flow dependency characteristics of this PET.
- Subjects :
- Isolation transformer
Materials science
business.industry
020208 electrical & electronic engineering
05 social sciences
Electrical engineering
02 engineering and technology
Converters
Zero voltage switching
Power (physics)
law.invention
Power flow
law
Power electronics
0202 electrical engineering, electronic engineering, information engineering
0501 psychology and cognitive sciences
Transformer
business
050107 human factors
Subjects
Details
- Database :
- OpenAIRE
- Journal :
- 2020 IEEE 9th International Power Electronics and Motion Control Conference (IPEMC2020-ECCE Asia)
- Accession number :
- edsair.doi...........57c094219963f2608acd733fa561d248
- Full Text :
- https://doi.org/10.1109/ipemc-ecceasia48364.2020.9368216