Back to Search Start Over

Making My Paper Mill Safer: An Arc-Flash Energy Reduction Story

Authors :
Haley Newton
Jordan McCrory
Source :
IEEE Transactions on Industry Applications. :1-1
Publication Year :
2020
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2020.

Abstract

A Midwestern pulp and paper mill had arc-flash ratings around 100 cal/cm2 on 50 480-V unit substations. New relays were installed to replace the existing protection and add light detection to improve arc-flash detection times. During a couple of one-day outages, sample installations took place. During the cold mill outage, 44 installations were completed over 12 days by working around the clock. Old relays were removed, new plates were mounted and wired in, and fiber sensors were routed through the buswork and into the breaker cubicles. Updated arc-flash studies show an average arc-flash rating reduction of 90%.

Details

ISSN :
19399367 and 00939994
Database :
OpenAIRE
Journal :
IEEE Transactions on Industry Applications
Accession number :
edsair.doi...........248c3efc34b1693fe20fea8cd10847f5
Full Text :
https://doi.org/10.1109/tia.2020.2986334