Back to Search
Start Over
Making My Paper Mill Safer: An Arc-Flash Energy Reduction Story
- Source :
- IEEE Transactions on Industry Applications. :1-1
- Publication Year :
- 2020
- Publisher :
- Institute of Electrical and Electronics Engineers (IEEE), 2020.
-
Abstract
- A Midwestern pulp and paper mill had arc-flash ratings around 100 cal/cm2 on 50 480-V unit substations. New relays were installed to replace the existing protection and add light detection to improve arc-flash detection times. During a couple of one-day outages, sample installations took place. During the cold mill outage, 44 installations were completed over 12 days by working around the clock. Old relays were removed, new plates were mounted and wired in, and fiber sensors were routed through the buswork and into the breaker cubicles. Updated arc-flash studies show an average arc-flash rating reduction of 90%.
- Subjects :
- Light detection
business.industry
Computer science
020208 electrical & electronic engineering
Energy reduction
Paper mill
02 engineering and technology
Industrial and Manufacturing Engineering
Automotive engineering
Control and Systems Engineering
SAFER
0202 electrical engineering, electronic engineering, information engineering
Arc flash
Mill
Electrical and Electronic Engineering
business
Circuit breaker
Subjects
Details
- ISSN :
- 19399367 and 00939994
- Database :
- OpenAIRE
- Journal :
- IEEE Transactions on Industry Applications
- Accession number :
- edsair.doi...........248c3efc34b1693fe20fea8cd10847f5
- Full Text :
- https://doi.org/10.1109/tia.2020.2986334