Customized wavelets for improved fault location quality in power systems

Authors :
Paraskevas E. Argyropoulos
Hanoch Lev-Ari
Source :
2013 IEEE Power and Energy Conference at Illinois (PECI).
Publication Year :
2013
Publisher :
IEEE, 2013.

Abstract

A procedure for generating customized wavelets for detecting the location of a fault along the length of a transmission line is proposed. Measuring the time-difference-of-arrival (TDOA) between two consecutive transient reflections or the TDOA between the two initial peaks of two synchronized voltage/current bus measurements provides an accurate fault location estimate. Highly accurate TDOA estimates can be obtained only when the processed fault waveform consists of short/peaked pulses that arrive on a bus with a small group delay. Our customization procedure enhances the “peakedness” and shortens the group delay of the transient waveform by optimizing a suitable peakedness metric. This approach yields more accurate estimates than the “classic” (Daubechies) wavelet-based techniques found in the literature. The proposed method is independent of the fault-type and can be used to reduce the required data sampling rate while maintaining reliable TDOA estimates.

Details

Database :
OpenAIRE
Journal :
2013 IEEE Power and Energy Conference at Illinois (PECI)
Accession number :
edsair.doi...........15adb7837688cc2d821b1a4e318e8fcf
Full Text :
https://doi.org/10.1109/peci.2013.6506062