Back to Search
Start Over
Customized wavelets for improved fault location quality in power systems
- Source :
- 2013 IEEE Power and Energy Conference at Illinois (PECI).
- Publication Year :
- 2013
- Publisher :
- IEEE, 2013.
-
Abstract
- A procedure for generating customized wavelets for detecting the location of a fault along the length of a transmission line is proposed. Measuring the time-difference-of-arrival (TDOA) between two consecutive transient reflections or the TDOA between the two initial peaks of two synchronized voltage/current bus measurements provides an accurate fault location estimate. Highly accurate TDOA estimates can be obtained only when the processed fault waveform consists of short/peaked pulses that arrive on a bus with a small group delay. Our customization procedure enhances the “peakedness” and shortens the group delay of the transient waveform by optimizing a suitable peakedness metric. This approach yields more accurate estimates than the “classic” (Daubechies) wavelet-based techniques found in the literature. The proposed method is independent of the fault-type and can be used to reduce the required data sampling rate while maintaining reliable TDOA estimates.
Details
- Database :
- OpenAIRE
- Journal :
- 2013 IEEE Power and Energy Conference at Illinois (PECI)
- Accession number :
- edsair.doi...........15adb7837688cc2d821b1a4e318e8fcf
- Full Text :
- https://doi.org/10.1109/peci.2013.6506062