Back to Search Start Over

A PMU-Based Method for On-Line Thévenin Equivalent Estimation

Authors :
Federico Milano
Hassan Haes Alhelou
Pourya Abdi
Mohamad Esmail Hamedani Golshan
Source :
IEEE Transactions on Power Systems. 37:2796-2807
Publication Year :
2022
Publisher :
Institute of Electrical and Electronics Engineers (IEEE), 2022.

Abstract

The paper proposes a technique for the on-line estimation of Thevenin equivalent (TE) which only needs the present phasor measurements. The technique is based on the wide-area measurements including voltage and current phasors of the system loads and synchronous generators, so that it can simultaneously estimate TE of the system seen from the interested buses. The technique has two main steps. In the first step, the conventional impedance matrix $\bar Z_{\rm bus}$ is modified to be suitable for TE estimation. In the second step, a correction coefficient based on the sensitivity theory calculated by using two consecutive phasor measurements is applied to correct the diagonal terms of the $\bar Z_{\rm bus}$ matrix. Simulation results carried on the IEEE 39-bus and 118-bus test systems show that the proposed technique can accurately estimate the TE for both generation and consumption buses under any load-increase scenario. The comparison scenarios verify the superiority of the proposed technique over others.

Details

ISSN :
15580679 and 08858950
Volume :
37
Database :
OpenAIRE
Journal :
IEEE Transactions on Power Systems
Accession number :
edsair.doi...........109d43923a224b7053bb0ac4669074a1
Full Text :
https://doi.org/10.1109/tpwrs.2021.3125007