Analysis of half-wavelength transmission line under critical balanced faults: Voltage response and overvoltage mitigation procedure
- Source :
- Electric Power Systems Research. 166:99-111
- Publication Year :
- 2019
- Publisher :
- Elsevier BV, 2019.
-
Abstract
- This paper presents a detailed study of half-wavelength (HWL) transmission line system under critical fault conditions. This non-conventional ultra high voltage alternating current (UHVAC) transmission line has excellent properties in steady-state operation condition and economic advantage when compared to conventional UHVAC system and even high voltage direct current (HVDC) transmission systems for similar power capacity. This technology has been studied for many decades and its response under condition fault is an important topic. First, the point of fault and the type of fault conditions are evaluated to confirm that balanced faults in specific regions are critical. Then the main characteristics of voltage response of HWL transmission system under balanced fault are presented and critical regions that produce severe overvoltage are identified and main transient characteristics are described. Finally, a preliminary mitigation procedure is shown and its performance is evaluated.
- Subjects :
- Computer science
020209 energy
020208 electrical & electronic engineering
Energy Engineering and Power Technology
02 engineering and technology
Transmission system
Fault (power engineering)
law.invention
Overvoltage
Transmission line
law
Control theory
0202 electrical engineering, electronic engineering, information engineering
Point (geometry)
High-voltage direct current
Transient (oscillation)
Electrical and Electronic Engineering
Alternating current
Subjects
Details
- ISSN :
- 03787796
- Volume :
- 166
- Database :
- OpenAIRE
- Journal :
- Electric Power Systems Research
- Accession number :
- edsair.doi...........04865ca251f2d64df6d98af1382f50a7
- Full Text :
- https://doi.org/10.1016/j.epsr.2018.10.002