Aging condition assessment of transformer oil-immersed cellulosic insulation based upon the average activation energy method

Authors :
Xianhao Fan
Yiyi Zhang
G. Ren
Wang Jiabao
Hanbo Zheng
Chuansheng Zhang
Benhui Lai
Enze Zhang
Jiefeng Liu
Source :
Cellulose. 26:3891-3908
Publication Year :
2019
Publisher :
Springer Science and Business Media LLC, 2019.

Abstract

It is widely accepted that the service life of transformer oil–paper insulation is determined by the aging condition of transformer cellulosic insulation. Therefore, it is rather meaningful to accurately and reliably evaluate the aging condition of transformer cellulose insulation. Existing studies have shown that activation energy can eliminate the temperature effect on the frequency dielectric spectroscopy, however, the traditional activation energy might not be suitable for assessing the aging condition of transformer cellulosic insulation. The aim of the work is to assess the aging condition of cellulosic insulation by using average activation energy technique. The experiment process is firstly discussed. Then, the second-order dynamic equation formed by Arrhenius equation and Ekenstam equation is strictly investigated to accurately calculate the degree of polymerization value of transformer cellulosic insulation. The experimental results preliminarily show that the average activation energy can effectively assess aging condition of transformer cellulosic insulation.